3 phase Online UPS Manufacturer 40KVA online low frequency ups with output isolate transformer
Low Frequency Online UPS
Technical Specifications
True Online Dual Conversion UPS
Built-in Galvanic Isolation Transformer
Field Proven Rugged design for tough power conditions
State of the art technology
IGBT based SPWM technology
Excellent warranty & post warranty support
Wide range of products from 1KVA to 300KVA
Wide input range
Compact size
High performance/High efficient design
Near unity input power factor
Excellent Voltage Regulation and Transient response
User friendly comprehensive LCD display and mimic diagram
Supports all types of batteries
Extended Run Time
Generator Compatible
After Sale support available in major cities across the country
Optional Intelligent Computer Interface and SNMP
Optional Auto Bypass (Static bypass)
Optional Parallel redundancy / Static redundancy
Applications
Office Automation
Data Centres
Building Management
Education Institutes
Telecommunication Centres
Satellite Earth Station
CNC Machines
Banking
Defence
R and D Centres
Bio-medical Equipments
Lift and Elevators
Industrial Instrumentation
Machine Tools
Security and surveillance equipments
Colour Lab Equipment
Photo Copying Machines
Printers and Plotters
Embroidery Machines
Medical Equipments
Diagnostic/Lab Equipments
Ultra Sonic Sonography Machines
ATM Centres
Parameter:
Model | GP3110K | GP3115K | GP3120K | GP3130K | GP3140K | |
Capacity | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | |
INPUT | ||||||
Norminal Voltage | 3*380VAC (3PH+G or 3PH +N+G) | |||||
Acceptable voltage range | 304VAC~456VAC | |||||
Frequency Range | 50Hz±5Hz(±10%) | |||||
OUTPUT | ||||||
Norminal voltage | 220VAC/230VAC/240VAC(Selectable) | |||||
Connection type | Hardwire 3-wire (1PH+N+G) | |||||
Waveform | Pure Sine wave | |||||
Output voltage stability | steady state | ±1% | ||||
Transient state | ±5% | |||||
Frequency | 50Hz | |||||
Frequency Synchronization range | ±1% | |||||
Frequency Synchronization speed | 1·2Hz/s | |||||
Power factor | 0.8 | |||||
Crest Factor | 3:01 | |||||
Total Harmonic Distortion(THDv) | ≤2% (linear load); ≤4% (non-linear load) | |||||
Dynamic in-rush voltage range | 0%->100%->0%(R load)<±5%; 20%->100%->20%(Rload)±3%; | |||||
Dynamic Recovery Time(III Grade) | 0~100% RCD load;<60ms recover to 90% of norminal voltage | |||||
Phase Displacement | 120°±1%(balanced load); 120°±2%(imbalances 50% of the load) | |||||
Transfer time | 0ms | |||||
Overload Capacity | 0~110% continuous running; 110%~150% for10min~1min;>160% for 200ms | |||||
Short-circuit capacity | 60~100ms | |||||
Transient response time | <5ms | |||||
BYPASS | ||||||
Connection Type | Hardwire 3-wire(1PH+N+G) | |||||
Input Voltage range | 220VAC±25% | |||||
Overload Capacity | 1.5In~1.8In 1h-30s | |||||
Short-circuit capacity | 1.8In~2.0In 30s~200ms | |||||
SYSTEM | ||||||
Efficiency(At linear load and 270VDC) | 85% | 86% | 86% | 88% | 89% | |
ECO mode(Non-parallel models) | Yes | |||||
EPO Function | Yes | |||||
Standard | IEC 61000-4-5 Protection surge;IEC62040-1 EMC/EMI, IEC62040-1 Safety | |||||
BATTERY | ||||||
Battery | Type | Support VRLA Battery | ||||
Number | 16-18pcs | |||||
Reverse Diode | Yes | |||||
Cold start | Yes | |||||
PHYSICAL | ||||||
IP Protection | IP20(Default),IP21/31(oPTIONAL) | |||||
Dimension,D×W×H (mm) | 570×450×900 | 700×450×1050 | ||||
Net Weight(KGS) | 125 | 135 | 200 | 280 | 310 | |
ENVIRONMENT | ||||||
Operating Temperature | 0~35℃ continuous running.40℃ 8hs running at nominal input voltage, recharging batteries and no overload, 45℃ derating to 85% with linear load | |||||
Humidity | 0~90% (Non-Condensing) | |||||
Noise level | less than 70dB @ 1 Meter | |||||
MAINTENANCE | ||||||
Modbus RS-232/RS485 | Support Windows 2000/2003/XP/Vista/2008/7/8,Linux and MAC | |||||
Dry contacts | 6 outputs and 2 inputs | |||||
Optional SNMP | Power management from SNMP manager and Web browser |