Add to Cart
Single Phase online ups for data center 1-3kva
| Model | HP1101H | HP1102H | HP1103H |
| Capacity | 1KVA/800W | 2KVA/1600W | 3KVA/2400W |
| Norminal voltage | 220VAC Single phase grounding | ||
| Norminal frequency | 50Hz | ||
| Input | |||
| Voltage Range | 115-300VAC | ||
| Frequency Range | 50Hz:(46-54Hz) | ||
| Power Factor | 0.99 | ||
| Output | |||
| Voltage Precision | 220VAC×(1±1%) | ||
| Frequency Precision | 50Hz×(1±1%) | ||
| Power factor | 0.8 | ||
| Harmonic Distortion | Linear load<3% Non-linear<6% | ||
| Overload Capability (AC 25°C) | 105%±5% <load≤150%±5% Transfer to bypass and Alarming after more than 1min;150%±5%<load<200%±5% Transfer to bypass and Alarming after more than 300ms; | ||
| Transfer time | 0 ms(AC mode↔Battery) ;<4 ms(AC mode↔ Bypass) | ||
| Battery | |||
| DC Voltage | 36VDC | 72VDC | 96VDC |
| Charging current | 6A | 7A | |
| Backup Time(Full Load) | Depends on external battery capacity | ||
| Panel Display | |||
| LED indicators | inverter, bypass, battery ,electricity ,load ,AC |
||
| Communication port | Smart RS232, SNMP (Optional) , AS400(Optional),CMC(Optional) | ||
| Working Environment | |||
| Temperature | 0°C-40°C | ||
| Relative Humidity | 20%-90%(non-condensing) | ||
| Storage Temperature | -25°C~55°C | ||
| Elevation | <1000m | ||
| Noise Level | <55dB | ||
| Physical Characteristic | |||
| Weight(KG) | 5.2 | 8.6 | 8.7 |
| Dimensions: ( W x D x H ) | 144×345×229 | 190×393×328 | |